ASHRAE Standard 241-2023 Equivalent Clean Airflow (ECA) Benchmark Dataset

Deterministic building ventilation and infectious aerosol mitigation benchmark dataset containing 178 multi-technology calculation vectors. Tabulates mandatory Equivalent Clean Airflow (ECA_i) baselines per occupant and floor area across 11 occupancy archetypes under ANSI/ASHRAE Standard 241-2023. Models central recirculated air filtration (MERV 8 through MERV 16/HEPA), in-room portable air cleaners (CADR), and upper-room germicidal UV-C irradiation.

๐Ÿ“ฅDownload CSV (33.4 KB)๐Ÿ“ŠView on Figshare Data Repository โ†—

๐Ÿ”ฌ Dataset Methodology & Engineering Basis

Synthesized using HVACLogic's deterministic ASHRAE 241 computational engine conforming to ANSI/ASHRAE Standard 241-2023 Section 5 (Assessment and Planning) and Section 6 (Equivalent Clean Airflow Rates and Air Cleaning Systems). Bioaerosol droplet nuclei capture efficiencies are evaluated from ASHRAE 52.2 particle size efficiency curves in the 1โ€“3 ยตm aerodynamic diameter band. Room air mixing effectiveness factors are fixed at ฮต_mix = 0.90 for localized portable HEPA filtration.

Governing Engineering Standards & Codes:

๐Ÿ›๏ธ ANSI/ASHRAE Standard 241-2023๐Ÿ›๏ธ ANSI/ASHRAE Standard 62.1-2022๐Ÿ›๏ธ ANSI/ASHRAE Standard 52.2-2017

๐Ÿ“‹ Tabular Data Preview (First 5 Rows)

Displaying 5 of 178 rows
vector_idspace_typecategoryfloor_area_sqftoccupantsceiling_height_ftroom_volume_cuftashrae_241_eca_p_cfmashrae_241_eca_a_cfmrequired_eca_cfmrequired_ach_equivoutdoor_air_cfmrecirc_air_cfmcentral_filter_mervfilter_bioaerosol_effdelivered_filter_eca_cfmin_room_cadr_cfmroom_mixing_factordelivered_in_room_eca_cfmuvc_eca_cfmtotal_delivered_eca_cfmdelivered_ach_equivcompliance_margin_cfmcompliance_ratioirmm_compliance_statusgoverning_standard
ECA-VEC-0001classroom_age_5_8Educational900259810042.40.1211688.72031148MERV 80.2229.600.900432.63.2-735.40.37CRITICAL_DEFICITANSI/ASHRAE Standard 241-2023 Table 5-1
ECA-VEC-0002classroom_age_5_8Educational900259810042.40.1211688.72031148MERV 80.2229.62500.92250657.64.9-510.40.563CRITICAL_DEFICITANSI/ASHRAE Standard 241-2023 Table 5-1
ECA-VEC-0003classroom_age_5_8Educational900259810042.40.1211688.72031148MERV 110.557400.9007775.8-3910.665CRITICAL_DEFICITANSI/ASHRAE Standard 241-2023 Table 5-1
ECA-VEC-0004classroom_age_5_8Educational900259810042.40.1211688.72031148MERV 110.55742500.9225010027.4-1660.858MARGINAL_DEFICITANSI/ASHRAE Standard 241-2023 Table 5-1
ECA-VEC-0005classroom_age_5_8Educational900259810042.40.1211688.72031148MERV 130.85975.800.9001178.88.710.81.009COMPLIANTANSI/ASHRAE Standard 241-2023 Table 5-1

๐Ÿ“– Data Dictionary & Variable Definitions

Complete schema definition describing each column, engineering unit of measure, data type, and thermodynamic description:

Variable NameData TypeUnitEngineering Description
vector_idstringโ€”Unique clean airflow calculation vector (ECA-VEC-0001 to ECA-VEC-0178)
space_typestringโ€”Occupancy archetype identifier per ASHRAE 241 Table 5-1
categorystringโ€”Broad building occupancy sector (Educational, Commercial, Healthcare, Public Assembly, Residential)
floor_area_sqftnumbersq ftNet occupied room usable floor area
occupantsnumberโ€”Zone design peak occupant population (P_z)
ceiling_height_ftnumberftFloor-to-ceiling clear architectural height
room_volume_cuftnumbercu ftTotal interior zone cubic volume
ashrae_241_eca_p_cfmnumberCFM/personTable 5-1 minimum equivalent clean airflow required per person
ashrae_241_eca_a_cfmnumberCFM/sq ftTable 5-1 minimum equivalent clean airflow required per unit floor area
required_eca_cfmnumberCFMTotal mandatory equivalent clean airflow demand during IRMM mode
required_ach_equivnumberACHRequired equivalent clean air exchange rate per hour
outdoor_air_cfmnumberCFMPathogen-free outdoor ventilation airflow delivery (V_ot)
recirc_air_cfmnumberCFMCentral recirculated airflow handled by the air-handling unit
central_filter_mervstringโ€”Installed central filtration rating (MERV 8, 11, 13, 14, 16/HEPA)
filter_bioaerosol_effnumberโ€”Single-pass removal efficiency on 1โ€“3 ยตm droplet nuclei
delivered_filter_eca_cfmnumberCFMEquivalent clean airflow delivered via central filtered recirculation
in_room_cadr_cfmnumberCFMTotal rated Clean Air Delivery Rate of in-room portable air cleaners
room_mixing_factornumberโ€”Room air mixing effectiveness factor (0.90)
delivered_in_room_eca_cfmnumberCFMEffective in-room portable clean airflow delivered
uvc_eca_cfmnumberCFMEquivalent clean airflow credited from upper-room UV-C irradiation
total_delivered_eca_cfmnumberCFMAggregate sum of all delivered equivalent clean airflow pathways
delivered_ach_equivnumberACHDelivered equivalent clean air changes per hour
compliance_margin_cfmnumberCFMCompliance surplus (+) or deficit (-) in CFM
compliance_rationumberโ€”Ratio of delivered ECA to required ECA (>= 1.0 indicates compliance)
irmm_compliance_statusstringโ€”Infection Risk Management Mode compliance classification
governing_standardstringโ€”Authoritative regulatory code standard

๐Ÿงฎ Interactive Companion Calculators

Test and explore these mathematical models dynamically in our client-side calculators:

Filter Sizing & Static Pressure Drop Calculator โ†’

Size MERV 13+ filters, calculate face velocity, and evaluate initial clean vs. loaded static pressure drops.

Ventilation Airflow & Building CFM Calculator โ†’

Determine building envelope sensible/latent airflow requirements and room air exchange rates.

๐ŸŽ“ Companion Research Whitepapers

Read the full mathematical derivations and thermodynamic proofs:

ANSI/ASHRAE Standard 241-2023: Equivalent Clean Airflow (ECA), Infection Risk Management Mode (IRMM), and Pathogen Mitigation Architecture โ†’

Technical research monograph articulating governing mathematical formulations for ECA and pathogen mitigation.

๐Ÿ“š Academic Citation & Replication

When referencing this benchmark dataset in academic publications, university course syllabi, or engineering technical reports, please cite as follows:

HVACLogic Open Engineering Research Group. (2026). ASHRAE Standard 241-2023 Equivalent Clean Airflow (ECA) Benchmark Dataset [Data set]. HVACLogic Open Science. https://doi.org/10.6084/m9.figshare.33977425

BibTeX Entry:

@dataset{hvaclogic_ashrae_241_clean_airflow_benchmarks,
  author = {{HVACLogic Open Engineering Research Group}},
  title = {ASHRAE Standard 241-2023 Equivalent Clean Airflow (ECA) Benchmark Dataset},
  year = {2026},
  publisher = {HVACLogic Open Science},
  url = {https://hvaclogic.org/datasets/ashrae-241-clean-airflow-benchmarks},
  doi = {10.6084/m9.figshare.33977425}
}