📊 CSV Benchmark Dataset540 Verified RecordsđŸ›Ąī¸ CC BY 4.0 InternationalDOI: 10.6084/m9.figshare.33753856 ↗

Confined Space Combustion Air Infiltration, Opening Free Area, and Gross Louver Sizing Benchmark Matrix

Standardized sizing matrix for appliance combustion air requirements per NFPA 54 / National Fuel Gas Code and IFGC Section 304. Evaluates confined space cubic volume thresholds (50 cu ft / 1,000 BTU/h), net free area openings, and louver gross dimensional sizing across metal, wood, and direct screen configurations.

đŸ“ĨDownload CSV (42.1 KB)📊View on Figshare Data Repository ↗🤗View on Hugging Face Datasets ↗

đŸ”Ŧ Dataset Methodology & Engineering Basis

Calculates volume sufficiency for fuel gas appliance rooms across burner firing rates from 25,000 to 300,000 BTU/h. Opening net free areas are calculated per code standards: All Air from Indoors (1 sq in / 1,000 BTU/h), Outdoor Vertical Ducts (1 sq in / 4,000 BTU/h), Outdoor Horizontal Ducts (1 sq in / 2,000 BTU/h), and Single Outdoor Opening (1 sq in / 3,000 BTU/h).

Governing Engineering Standards & Codes:

đŸ›ī¸ NFPA 54 / ANSI Z223.1 (National Fuel Gas Code)đŸ›ī¸ International Fuel Gas Code (IFGC Section 304)đŸ›ī¸ CSA B149.1 (Natural Gas and Propane Installation Code)

📋 Tabular Data Preview (First 5 Rows)

Displaying 5 of 540 rows
vector_idtotal_input_bturoom_vol_cuftreq_unconfined_vol_cuftis_confined_spacevol_deficit_cuftlouver_typeindoor_2op_net_sqinindoor_2op_gross_sqinoutdoor_vert_2op_net_sqinoutdoor_vert_2op_gross_sqin
CA-VEC-0001250002881250TRUE962metal1001331013
CA-VEC-0002250002881250TRUE962wood1004001040
CA-VEC-0003250002881250TRUE962direct_screen1001001010
CA-VEC-0004250003841250TRUE866metal1001331013
CA-VEC-0005250003841250TRUE866wood1004001040

📖 Data Dictionary & Variable Definitions

Complete schema definition describing each column, engineering unit of measure, data type, and thermodynamic description:

Variable NameData TypeUnitEngineering Description
vector_idstring—Unique combustion scenario vector (CA-VEC-0001 to CA-VEC-0540)
total_input_btunumberBTU/hTotal appliance burner input firing rate (25,000 to 300,000 BTU/h)
room_len_ftnumberftEnclosure room length in feet
room_wid_ftnumberftEnclosure room width in feet
room_hgt_ftnumberftEnclosure room ceiling height in feet
room_vol_cuftnumbercu ftEnclosure interior cubic volume
req_unconfined_vol_cuftnumbercu ftCode required unconfined threshold volume (50 cu ft / 1,000 BTU/h)
is_confined_spaceboolean—Flag indicating whether room volume is deficient under NFPA 54
vol_deficit_cuftnumbercu ftNet cubic volume deficiency requiring exterior combustion air
louver_typestring—Louver construction material (metal, wood, direct_screen)
indoor_2op_net_sqinnumbersq inNet free area required for all-air-from-indoors two-opening method
indoor_2op_gross_sqinnumbersq inGross louver area accounting for free area ratio
outdoor_vert_2op_net_sqinnumbersq inNet free area for outdoor vertical ducts (1 sq in / 4,000 BTU/h)
outdoor_vert_2op_gross_sqinnumbersq inGross louver opening area for vertical ducts
outdoor_horiz_2op_net_sqinnumbersq inNet free area for outdoor horizontal ducts (1 sq in / 2,000 BTU/h)
outdoor_horiz_2op_gross_sqinnumbersq inGross louver opening area for horizontal ducts
outdoor_single_net_sqinnumbersq inNet free area for direct single opening to outdoors
outdoor_single_gross_sqinnumbersq inGross louver opening area for single opening

🧮 Interactive Companion Calculators

Test and explore these mathematical models dynamically in our client-side calculators:

Combustion Air & Confined Space Sizer →

Calculate room volume confinement, required free area, and louver dimensions.

🎓 Companion Research Whitepapers

Read the full mathematical derivations and thermodynamic proofs:

Multi-Zone Mass-Balance Ventilation and Continuous IAQ Dilution →

Technical paper analyzing building enclosure infiltration and combustion air dynamics.

📚 Academic Citation & Replication

When referencing this benchmark dataset in academic publications, university course syllabi, or engineering technical reports, please cite as follows:

HVACLogic Open Engineering Research Group. (2026). Confined Space Combustion Air Infiltration, Opening Free Area, and Gross Louver Sizing Benchmark Matrix [Data set]. HVACLogic Open Science. https://doi.org/10.6084/m9.figshare.33753856

BibTeX Entry:

@dataset{hvaclogic_combustion_air_confined_space,
  author = {{HVACLogic Open Engineering Research Group}},
  title = {Confined Space Combustion Air Infiltration, Opening Free Area, and Gross Louver Sizing Benchmark Matrix},
  year = {2026},
  publisher = {HVACLogic Open Science},
  url = {https://hvaclogic.org/datasets/combustion-air-confined-space},
  doi = {10.6084/m9.figshare.33753856}
}